Yes. While differences caused by the gap in accuracy class and sensitivity between the main building meter and individual meters are fully justified, they can be amplified by several factors, such as:
1. Water losses in the building’s common installation (between the main meter and individual meters)
A continuous water flow as small as 3 mm can result in a loss of 26 m³/month. In most cases, such leaks are visible (e.g., water accumulating in the basement), but there may also be hidden leaks, where the water infiltrates directly into the ground. In these cases, detection can be done by closing all vertical risers and checking if the main meter still records a continuous flow.
2. Permanent low-flow leaks in individual installations
A single faucet or toilet with a constant flow of 5.99 l/h (below the starting flow of 6 l/h) can cause an undetected loss of 4.3 m³/month per apartment. The more low-flow leaks exist in individual installations, the greater the overall difference between the main and individual meter readings.
3. Difference between allocated and actual consumption in unmetered apartments
The actual consumption in unmetered apartments can far exceed the allocated amount based on the regulated consumption norm (5.1 m³/person/month for cold water and 3.3 m³/person/month for hot water).
If the number of residents in an unmetered apartment increases without the association being informed, the allocated consumption remains artificially low.
If there is a permanent leak (e.g., a faucet or toilet running continuously), real consumption can reach hundreds of cubic meters per month.
4. Difference between allocated and actual consumption in apartments with old meters
If an apartment uses old meters but is still considered “metered,” there’s no guarantee those meters still measure accurately or comply with metrological standards. Real consumption may be significantly higher than the recorded one.
5. Blockage of the individual meter’s turbine by debris
A water meter may fail to record not only when unused but also if the turbine is blocked by impurities.
This often occurs after maintenance work on the water network. A blocked meter is not covered by warranty and cannot be detected through radio reading. If combined with a permanent leak, undetected losses can be significant.
The association can periodically check for meters with zero consumption (new index – old index = 0) to identify possible blockages.
6. Fraudulent actions
Meters with radio modules installed by the company are sealed with uniquely numbered steel wire and detect magnetic tampering or reverse flow. Fraud attempts (e.g., bypassing, intentional blocking, seal breaking) can be easily detected through a simple visual check by the homeowners’ association.
7. Unmetered water sources in common spaces
Any unmetered source in shared areas will contribute to the difference between main and individual readings.
8. Time gap between main and individual meter readings
This cause has a limited and reversible effect: the difference evens out automatically in the next billing cycle.
9. Supplier billing based on estimated, not actual, consumption
If the hot water bill includes a three-letter code in the “Observations” section, it means the supplier has estimated the consumption (e.g., SIE – suspected error, COF – fraud, REF – access refused, etc.). The association must contact the supplier to resolve the cause of the estimate.
10. Incorrect or non-standard connection of the main meter
In rare cases, a building’s main meter may also record consumption from neighboring buildings, leading to inflated bills.
11. Main meter serial number errors between neighboring buildings
It’s possible (though unlikely) for the supplier to have swapped main meter serial numbers between adjacent buildings, resulting in incorrect billing.
12. Meters exceeding their recommended service life
After extended use, many individual meters may develop negative measurement errors due to turbine wear or blockage.
Before deciding on metrological verification or replacement, all other potential causes listed above should be ruled out.